Insulation Calculator
Insulation thickness needed to hit a target R-value for any material and wall area.
Written by Golam Rabbani, Founder & Lead Engineer
How to use this insulation calculator
- Toggle imperial (ft) or metric (m) for the wall dimensions.
- Enter the wall length and wall height — the area is calculated automatically.
- Set your target R-value (R-13 for a 2×4 wall, R-19 for a 2×6, R-30+ for an attic).
- Pick the insulation material from the dropdown.
- Press Calculate to see the thickness needed and the wall area.
About this insulation calculator
The insulation calculator finds the thickness needed to hit a target R-value for nine common insulation materials. R-value measures thermal resistance: higher means better. The formula is thickness (in inches) = target R ÷ R-per-inch of the chosen material. R-per-inch values are published by the US Department of Energy: fiberglass batt 3.2, mineral wool batt 3.7, cellulose loose-fill 3.5, EPS rigid foam 3.8, XPS rigid 5.0, polyiso rigid 6.0, open-cell spray foam 3.7, and closed-cell spray foam 6.5.
Worked example: a 40 ft × 8 ft wall needs to hit R-19 (a typical 2×6 cavity target). With fiberglass batt at R-3.2 per inch, thickness needed = 19 ÷ 3.2 = 5.94 inches — perfect for a 5.5″ 2×6 cavity. Using closed-cell spray foam at R-6.5/in, you only need 2.93 inches, leaving room for additional fill or ventilation. Wall area is 320 ft², so you would buy enough material to cover that area at the chosen thickness.
Match thickness to your cavity. A 2×4 wall (3.5″ actual) maxes out around R-13 batt or R-21 closed-cell foam. A 2×6 (5.5″) reaches R-19 batt or R-35 closed-cell. Attics typically target R-38 to R-60 in cold climates; check the US DOE recommended R-value map for your IECC climate zone before settling on a target.
FAQ
- What R-value do I need?
- US DOE recommends R-13 to R-21 for walls and R-30 to R-60 for attics depending on climate zone. Cold climates use the higher numbers, mild climates the lower. Always check current local code.
- Which insulation has the highest R per inch?
- Closed-cell spray foam (~R-6.5/in) and polyiso rigid board (~R-6.0/in) lead. Fiberglass batt is ~R-3.2/in; cellulose loose-fill ~R-3.5/in.
- Why does material choice matter beyond R-value?
- Spray foam doubles as an air seal; batts do not. Rigid foam can be installed outside the framing to break thermal bridging. Cellulose dampens sound better than fiberglass. Each material has trade-offs in cost, install complexity, fire rating, and vapor permeability.
- Can I exceed my cavity depth?
- Only with a furred-out wall or by adding rigid foam on the exterior. Compressing batts below the rated thickness reduces R-value — never stuff R-19 batts into a 2×4 cavity.
- Are these R-values code-compliant?
- They are the published DOE/ASHRAE typical values, but local codes (IECC, IRC) and energy programs (ENERGY STAR, LEED) may require different minimums. Always confirm with your building department.
- Is this calculator free?
- Yes — free, runs in your browser, no signup.